Three Phase380VAC DC 110V Rectifier With 94% Efficiency And 20A Output TH110D20NZ-6
| Input Voltage: | Three-phase380VAC(-15%~+20%) | Input Frequency: | 45~55Hz |
| Output Voltage Range: | 88~150VDC | Current Limit Setting Range: | 2~22A |
| Efficiency: | Peak Efficiency≥94% | Power Factor: | Full Load≥0.95 |
| Voltage Regulation Accuracy: | ≤±0.5% | Cooling Method: | Fan Cooling |
| High Light: | 94% Efficiency 110V DC Rectifier,20A Output Current High-Frequency Switching Power Supply,RS-485 Communication Interface Industrial Power Module |
||
| Model Number | TH110D20NZ-6 | Brand Name | TONHE |
|---|---|---|---|
| Input Voltage | 323-456VAC/380 | Output Current | 20A |
| Output Voltage | 88-150VDC/110 | Power | 2.2 KW |
| Parallel Operation | ≤±3% | Efficiency | ≥94% |
| Voltage Stabilization | ≤±0.5% | Ripple Coefficient | ≤0.5% |
| Current Stabilization | ≤1% | Cooling | Fan cooling |
| Dimensions (L*W*H) | 342*237*89mm | Noise Level | ≤60dB |
| Warranty | 12 months | Place of Origin | HeBei, China |
- High Efficiency: Achieves over 94% peak efficiency and power factor ≥0.95, reducing energy costs and grid pollution
- Intelligent & Manageable: Supports full remote "Four-Remote" control via RS-485 interface, ideal for unattended sites
- Robust & Reliable: Features comprehensive protections and supports N+1 hot-swappable redundancy for maximum system uptime
- Compact & Standardized: Small size saves space and complies with DL/T 781-2021 industry standards
| Parameter | Specification |
|---|---|
| Input Voltage | Three-phase 380VAC (-15%~+20%) |
| Input Frequency | 45~55Hz |
| Output Voltage Range | 88~150VDC |
| Current Limit Setting Range | 2~22A |
| Efficiency | Peak Efficiency ≥94% |
| Power Factor | Full Load ≥0.95 |
| Voltage Regulation Accuracy | ≤±0.5% |
| Current Regulation Accuracy | ≤±1% |
| Peak-to-Peak Ripple Factor | ≤0.5% |
| Output Noise (Peak-to-Peak) | At Rated Condition ≤60dB |
| Current Sharing Imbalance | ≤±3% |
| Soft Start Time | 3~8S |
| Storage Temperature | -40~+60℃ |
| Operating Temperature | -10~+40℃ |
| Cooling Method | Forced Air Cooling |
Automatic Current Limiting: Once output current reaches the set limit, the module automatically switches to constant current operation.
Overvoltage Protection: Software-based protection with configurable alarm settings that can initiate output shutdown.
Short-Circuit Protection: Enters self-protective foldback mode during output short circuits and automatically resumes normal operation once fault is cleared.
Insulation Strength:
Input to Chassis: 2100VAC 1 min, Earth Leakage Current ≤10mA
Output to Chassis: 2100VAC 1 min, Earth Leakage Current ≤10mA
Input to Output: 2100VAC 1 min, Earth Leakage Current ≤10mA
Insulation Resistance: ≥10MΩ (1000V Insulation Resistance Test)
- Electric Power Facilities: Substations, power plants, and hydropower stations
- Industrial & Infrastructure: Plant control systems, data center backup power, and telecommunications infrastructure