RS485 Communication 220V DC Rectifier With 5A Output Current Fanless Design TH230D05ZZ-3
| Model Number: | TH230D05ZZ-3G | Input Voltage: | 304V-456VAC/380V |
| Output Current: | 5A | Noisy: | ≤55dB |
| Power: | 1.5KW | Efficiency: | ≥93% |
| Cooing: | Natural Cooling | 220v dc rectifier: | 220v Dc Rectifier |
| Input Voltage | 304V-456VAC/380V | Output Current | 5A |
|---|---|---|---|
| Output Voltage | 190V-300VDC/220V | Noise Level | ≤55dB |
| Model Number | TH230D05ZZ-3 | Brand Name | TONHE |
| Output Frequency | 50 Hz | Efficiency | ≥93% |
| Power Factor | ≥0.93 | Communication Protocol | RS485 |
| Power Rating | 1.5KW | Cooling Method | Natural Cooling |
| Ripple Coefficient | ≤1% | Voltage Stabilization Accuracy | ≤±0.5% |
| Dimensions | 325*139*263 mm | Soft Start Time | 3-8 S |
- Perfect Fit for Wall-Mounted Cabinets: Compact dimensions (260*179*109mm) with fanless design, ideal for space-constrained wall-mounted power systems. Eliminates need for large ventilation ducts.
- Maintenance-Free & Silent Operation: Natural convection cooling ensures zero noise operation, perfect for indoor substations or office environments, while preventing dust accumulation.
- Industrial "Four Remote" Functions: Standard RS-485 interface for seamless SCADA integration. Monitor voltage/current, receive fault signals, and control output remotely for unattended operations.
- High Reliability & Efficiency: Resonant Voltage Mode Control technology achieves up to 95% efficiency. Stable 230VDC output in harsh industrial environments (-10℃ to +40℃).
- Plug-and-Play Protection: Comprehensive protection including Foldback Short-Circuit Protection, Over-Temperature, and Output Over-Voltage lockout.
|
Item |
230D05ZZ-3 |
230D07ZZ-3 |
230D10ZZ-3 |
230D20ZZ-3 |
230D20NZ-3 |
230D30NZ-3 |
230D40NZ-3 |
||
|
Output Current (A) |
5 |
10 |
10 |
20 |
20 |
30 |
40 |
||
|
Power (kW) |
1.5 |
2.1 |
3 |
6 |
6 |
9 |
12 |
||
|
Weight (kg) |
5.2 |
9 |
9 |
16 |
10.5 |
19 |
19 |
||
|
Cooling Method |
Natural cooling |
Natural cooling |
Natural cooling |
Forced air cooling |
Forced air cooling |
Forced air cooling |
Forced air cooling |
||
|
Internal Heat Sink Temp. Rise |
≤30℃ |
≤30℃ |
≤30℃ |
≤20℃ |
≤20℃ |
≤20℃ |
≤20℃ |
||
|
|
Item |
Specification |
|||||||
|
|
Input Voltage Range (VAC) |
Min: 304 / Typ: 380 / Max: 456 |
|||||||
|
|
Output Adjustable Range (VDC) |
Min: 190 / Typ: 220 / Max: 300 |
|||||||
|
|
Voltage Regulation Accuracy |
±0.5% |
|||||||
|
|
Current Regulation Accuracy |
±1% |
|||||||
|
|
Input Power Factor |
≥0.93 |
|||||||
|
|
Charger Efficiency |
≥95% |
|||||||
|
|
Maximum Audible Noise (dB) |
50 |
|||||||
|
|
Storage Temperature (℃) |
Min: -40 / Typ: 25 / Max: 60 |
|||||||
|
|
Operating Ambient Temperature (℃) |
Min: -10 / Typ: 25 / Max: 40 |
|||||||
|
|
Current Unbalance in Parallel |
≤±3% |
|||||||
|
|
Startup Delay (Seconds) |
3~8 |
|||||||
|
|
Ripple Coefficient |
≤0.2% |
|||||||
|
|
Load Level |
Class I (Continuous operation at 100% rated output current) |
|||||||
|
|
Automatic Current Limiting |
When output current exceeds the set current limit value, the charger switches to constant current output and the current will not increase. |
|||||||
|
|
Output Overvoltage Protection |
Automatically stops output when output voltage exceeds 320±5 VDC to prevent equipment damage. |
|||||||
|
|
Output Short Circuit Protection |
The module self-protects during an output short circuit to prevent damage; it can automatically resume normal operation once the fault is cleared. |
|||||||
|
|
Note |